Electrical Metallic Tubing (EMT) • Thin-Wall Conduit
Standard commercial and residential indoor metal raceway (NEC Chapter 9 Table 4)
1/2" EMT • #14 AWG THHN
Max Wires (40%):12 Wires
Actual Fill:38.3%
Usable 40% Area:0.122 sq in
Ampacity Derating:50%
NEC Ch. 9 CompliantView Schedule →
1/2" EMT • #12 AWG THHN
Max Wires (40%):9 Wires
Actual Fill:39.4%
Usable 40% Area:0.122 sq in
Ampacity Derating:70%
NEC Ch. 9 CompliantView Schedule →
1/2" EMT • #10 AWG THHN
Max Wires (40%):5 Wires
Actual Fill:34.7%
Usable 40% Area:0.122 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
3/4" EMT • #14 AWG THHN
Max Wires (40%):21 Wires
Actual Fill:38.2%
Usable 40% Area:0.213 sq in
Ampacity Derating:45%
NEC Ch. 9 CompliantView Schedule →
3/4" EMT • #12 AWG THHN
Max Wires (40%):16 Wires
Actual Fill:39.9%
Usable 40% Area:0.213 sq in
Ampacity Derating:50%
NEC Ch. 9 CompliantView Schedule →
3/4" EMT • #10 AWG THHN
Max Wires (40%):10 Wires
Actual Fill:39.6%
Usable 40% Area:0.213 sq in
Ampacity Derating:50%
NEC Ch. 9 CompliantView Schedule →
3/4" EMT • #8 AWG THHN
Max Wires (40%):5 Wires
Actual Fill:34.3%
Usable 40% Area:0.213 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
3/4" EMT • #6 AWG THHN
Max Wires (40%):4 Wires
Actual Fill:38%
Usable 40% Area:0.213 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
1" EMT • #12 AWG THHN
Max Wires (40%):26 Wires
Actual Fill:40%
Usable 40% Area:0.346 sq in
Ampacity Derating:45%
NEC Ch. 9 CompliantView Schedule →
1" EMT • #10 AWG THHN
Max Wires (40%):16 Wires
Actual Fill:39.1%
Usable 40% Area:0.346 sq in
Ampacity Derating:50%
NEC Ch. 9 CompliantView Schedule →
1" EMT • #8 AWG THHN
Max Wires (40%):9 Wires
Actual Fill:38.1%
Usable 40% Area:0.346 sq in
Ampacity Derating:70%
NEC Ch. 9 CompliantView Schedule →
1" EMT • #6 AWG THHN
Max Wires (40%):6 Wires
Actual Fill:35.2%
Usable 40% Area:0.346 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
1" EMT • #4 AWG THHN
Max Wires (40%):4 Wires
Actual Fill:38.1%
Usable 40% Area:0.346 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
1" EMT • #2 AWG THHN
Max Wires (40%):2 Wires
Actual Fill:26.8%
Usable 40% Area:0.346 sq in
Ampacity Derating:100%
NEC Ch. 9 CompliantView Schedule →
1-1/4" EMT • #6 AWG THHN
Max Wires (40%):11 Wires
Actual Fill:37.3%
Usable 40% Area:0.598 sq in
Ampacity Derating:50%
NEC Ch. 9 CompliantView Schedule →
1-1/4" EMT • #4 AWG THHN
Max Wires (40%):7 Wires
Actual Fill:38.6%
Usable 40% Area:0.598 sq in
Ampacity Derating:70%
NEC Ch. 9 CompliantView Schedule →
1-1/4" EMT • #3 AWG THHN
Max Wires (40%):6 Wires
Actual Fill:39%
Usable 40% Area:0.598 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
1-1/4" EMT • #2 AWG THHN
Max Wires (40%):5 Wires
Actual Fill:38.7%
Usable 40% Area:0.598 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
1-1/4" EMT • 1/0 AWG THHN
Max Wires (40%):3 Wires
Actual Fill:37.2%
Usable 40% Area:0.598 sq in
Ampacity Derating:100%
NEC Ch. 9 CompliantView Schedule →
1-1/2" EMT • #4 AWG THHN
Max Wires (40%):9 Wires
Actual Fill:36.4%
Usable 40% Area:0.814 sq in
Ampacity Derating:70%
NEC Ch. 9 CompliantView Schedule →
1-1/2" EMT • #2 AWG THHN
Max Wires (40%):7 Wires
Actual Fill:39.8%
Usable 40% Area:0.814 sq in
Ampacity Derating:70%
NEC Ch. 9 CompliantView Schedule →
1-1/2" EMT • 1/0 AWG THHN
Max Wires (40%):4 Wires
Actual Fill:36.4%
Usable 40% Area:0.814 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
1-1/2" EMT • 2/0 AWG THHN
Max Wires (40%):3 Wires
Actual Fill:32.8%
Usable 40% Area:0.814 sq in
Ampacity Derating:100%
NEC Ch. 9 CompliantView Schedule →
2" EMT • #2 AWG THHN
Max Wires (40%):11 Wires
Actual Fill:38%
Usable 40% Area:1.342 sq in
Ampacity Derating:50%
NEC Ch. 9 CompliantView Schedule →
2" EMT • 1/0 AWG THHN
Max Wires (40%):7 Wires
Actual Fill:38.7%
Usable 40% Area:1.342 sq in
Ampacity Derating:70%
NEC Ch. 9 CompliantView Schedule →
2" EMT • 4/0 AWG THHN
Max Wires (40%):4 Wires
Actual Fill:38.6%
Usable 40% Area:1.342 sq in
Ampacity Derating:80%
NEC Ch. 9 CompliantView Schedule →
Rigid PVC Conduit (Schedule 40) • Underground & Wet Locations
Heavy-wall non-metallic conduit with slightly thicker walls than EMT
1/2" PVC • #12 AWG THHN
Max Wires (40%):8 Wires
Actual Fill:37.3%
Usable 40% Area:0.114 sq in
Ampacity Derating:70%
Direct Burial RatedView Schedule →
3/4" PVC • #12 AWG THHN
Max Wires (40%):15 Wires
Actual Fill:39.3%
Usable 40% Area:0.203 sq in
Ampacity Derating:50%
Direct Burial RatedView Schedule →
3/4" PVC • #10 AWG THHN
Max Wires (40%):9 Wires
Actual Fill:37.4%
Usable 40% Area:0.203 sq in
Ampacity Derating:70%
Direct Burial RatedView Schedule →
3/4" PVC • #8 AWG THHN
Max Wires (40%):5 Wires
Actual Fill:36%
Usable 40% Area:0.203 sq in
Ampacity Derating:80%
Direct Burial RatedView Schedule →
1" PVC • #6 AWG THHN
Max Wires (40%):6 Wires
Actual Fill:36.6%
Usable 40% Area:0.333 sq in
Ampacity Derating:80%
Direct Burial RatedView Schedule →
1-1/4" PVC • #2 AWG THHN
Max Wires (40%):5 Wires
Actual Fill:39.8%
Usable 40% Area:0.581 sq in
Ampacity Derating:80%
Direct Burial RatedView Schedule →
2" PVC • 4/0 AWG THHN
Max Wires (40%):4 Wires
Actual Fill:39.3%
Usable 40% Area:1.316 sq in
Ampacity Derating:80%
Direct Burial RatedView Schedule →